marcgeld avatar marcgeld commented on May 31, 2024

I have a simular problem. I have two LOGO!8 230RCE with ip 10.0.0.90 and ip 10.0.0.91.
The one with ip 10.0.0.90 works well but the second one has problem connecting and I keep getting: "Error connecting to PLC: Error: connect EHOSTUNREACH 10.0.0.91:102" in node-red.

When I use curl to connect I don't se any connection problems (curl telnet://10.0.0.91:102).

Is there possibly a problem handling two devices simultaneously?

from node-red-contrib-s7.

gfcittolin avatar gfcittolin commented on May 31, 2024

@ccy527 ECONNRESET usually means the PLC rejected the connection. Unfortunately we currently can't tell why (there's a major refactor going on in the underlying library which will allow us to do so).
Maybe you can verify the diagnosis either at Step7 or at TIA Portal and check the used/free resources. Which PLC do you have?

from node-red-contrib-s7.

gfcittolin avatar gfcittolin commented on May 31, 2024

@marcgeld Unfortunately, I don't have two different PLCs to simulate here in the office, but I tried two connections to the same device without a problem. I also remember to have already connected to 2 different PLCs in the field without a problem.

Despite everything, I'd say EHOSTUNREACH would indicate a network/routing problem (even though it seems to be pretty unlikely given your setup). Dumb question, but have you tried to curl from the same machine where Node-RED was installed? I'm out of ideas why this may be happening :( Maybe you can try to sniff the communication with Wireshark or try another tool to investigate the issue. I'll let you know if I have any idea to debug this

from node-red-contrib-s7.

marcgeld avatar marcgeld commented on May 31, 2024

I’ll try debug using Wireshark. And yes I have tried the connectivity from inside the Node-red Docker image. The thing is that I am quite sure that this has been working well earlier.

Anyway, thanks for your node-red plug-in!!

from node-red-contrib-s7.

ccy527 avatar ccy527 commented on May 31, 2024

I’ll try debug using Wireshark. And yes I have tried the connectivity from inside the Node-red Docker image. The thing is that I am quite sure that this has been working well earlier.

Anyway, thanks for your node-red plug-in!!

@marcgeld Did you solve your problem ?
If you solved, could you please share your solution to me ?
Thank you very much for your help.

from node-red-contrib-s7.

ccy527 avatar ccy527 commented on May 31, 2024

@ccy527 ECONNRESET usually means the PLC rejected the connection. Unfortunately we currently can't tell why (there's a major refactor going on in the underlying library which will allow us to do so).
Maybe you can verify the diagnosis either at Step7 or at TIA Portal and check the used/free resources. Which PLC do you have?

@gfcittolin It's S7-317.
I am still checking is it the connection resource problem.
Thank you very much for your help.

from node-red-contrib-s7.

ccy527 avatar ccy527 commented on May 31, 2024

@gfcittolin
I got interesting result.
When I power up, 2 S7 node show online both, and can read data.
BUT, after I do some modification in node-red and click "Deploy".
192.168.0.100 changed to offline, 192.168.0.200 keep online.
I need to restart node-red then 192.168.0.100 go to online again.
Any idea ?
Thanks.

from node-red-contrib-s7.

gfcittolin avatar gfcittolin commented on May 31, 2024

There's a chance that what you're experiencing is being caused by a connection leakage of the nodes7 library when dropping the connection. I've just worked on a fix for it, and as soon as we have a new release I'll kindly ask you guys to try it out. If the problem still persists, maybe we can try to investigate a bit more with logs and wireshark captures

from node-red-contrib-s7.

MaFoB avatar MaFoB commented on May 31, 2024

Thank you for node-red-contrib-s7, Guilherme !
I have experienced a behaviour similar to ccy527's comment on 31 Jan with more than 1 S7 currently using 1.6.0 @ node-red v0.20.5 <=> Should it be fixed there, already?

from node-red-contrib-s7.

gfcittolin avatar gfcittolin commented on May 31, 2024

There shouldn't be connection problems anymore. 😕 Does the issue happens only when two connections are made to different PLCs at the same time?
If possible, could you please enable the debug mode, simulate the issue, and then post the logs here?

from node-red-contrib-s7.

MaFoB avatar MaFoB commented on May 31, 2024

The issue happens when connections are made to more than 1 different PLCs at the same time.
By now, I could not reproduce it significantly. Additionally, a SIEMENS OPC UA Server is reading variables out of all those PLCs at the same time. After having excluded this influence next week I will come up with logs in case the issue will not be solved then.

By the way: Do you have some hints for choosing an adequate node-s7 setup for connection cycle time (default 500ms) and timeout (default 1500ms) depending on the number of variables or other relevant boundary conditions ?

from node-red-contrib-s7.

gfcittolin avatar gfcittolin commented on May 31, 2024

It depends a lot on the type/amount of variables you're reading, how sparse they are, and on the network you're in.
The bigger/wider the variables (e.g BOOL vs DWORD), the sparser they are (e.g. all in a contiguous DB vs scattered around multiple memory areas) and the slower your network is (mainly regarding ping times, not throughput) , the more it will cost you to perform a read cycle, and therefore the less often you can read them. The actual values will of course depend you your environment.

Let me know then if you can simulate the connection issue.

from node-red-contrib-s7.

MaFoB avatar MaFoB commented on May 31, 2024

Good news: OPC UA Server disabled => the connections work fine :)
For the test, I have chosen a cycle time of 5000ms (with timeout 1500ms) and will keep the setup like that.
OPC UA Server enabled again => most connections still stable, some not. - Well, just good to know.

from node-red-contrib-s7.

MaFoB avatar MaFoB commented on May 31, 2024

More good news: We found and disabled another visualisation agent which was looking into the PLCs. After that, connections remain stable now.
My part of this issue is supposed to be solved then.

from node-red-contrib-s7.

gfcittolin avatar gfcittolin commented on May 31, 2024

Thanks for sharing your findings. Looks like there's no issue with the Node anymore, therefore I'm closing the issue.

Feel free to continue any discussion related to the topic or reopen it in case of other issues.

from node-red-contrib-s7.

Related Issues (20)

Recommend Projects

  • React photo React

    A declarative, efficient, and flexible JavaScript library for building user interfaces.

  • Vue.js photo Vue.js

    🖖 Vue.js is a progressive, incrementally-adoptable JavaScript framework for building UI on the web.

  • Typescript photo Typescript

    TypeScript is a superset of JavaScript that compiles to clean JavaScript output.

  • TensorFlow photo TensorFlow

    An Open Source Machine Learning Framework for Everyone

  • Django photo Django

    The Web framework for perfectionists with deadlines.

  • D3 photo D3

    Bring data to life with SVG, Canvas and HTML. 📊📈🎉

Recommend Topics

  • javascript

    JavaScript (JS) is a lightweight interpreted programming language with first-class functions.

  • web

    Some thing interesting about web. New door for the world.

  • server

    A server is a program made to process requests and deliver data to clients.

  • Machine learning

    Machine learning is a way of modeling and interpreting data that allows a piece of software to respond intelligently.

  • Game

    Some thing interesting about game, make everyone happy.

Recommend Org

  • Facebook photo Facebook

    We are working to build community through open source technology. NB: members must have two-factor auth.

  • Microsoft photo Microsoft

    Open source projects and samples from Microsoft.

  • Google photo Google

    Google ❤️ Open Source for everyone.

  • D3 photo D3

    Data-Driven Documents codes.